Connect-Tek Transa PRO 17 Bedienerhandbuch Seite 38

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 92
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 37
34
3–13 Sensor Break Alarm
Alarm 1 or alarm 2 can be configured as a sensor break alarm by selecting SENB
for A1FN or A2FN. If alarm 2 is required as a sensor break alarm, then
AL2 should be selected for OUT2. The sensor break alarm is activated as soon
as failure mode occurs. Refer to section 3-16 for failure mode conditions. Note
that A-D failure also creates a sensor break alarm. TIME, A1SP, A1DV, and
A1HY are hidden if alarm 1 is configured as a sensor break alarm. Similarly,
TIME, A2SP, A2DV and A2HY are hidden if alarm 2 is configured as a sensor
break alarm. One of four kinds of alarm modes can be selected for sensor break
alarm. These are: normal alarm, latching alarm, holding alarm and
latching/holding alarm. However, the holding alarm and latching/holding alarm
are not recommended for sensor break alarm since sensor break alarm will not
perform the holding function even if it is set for holding or latching/holding
mode. See section 3-8 for the descriptions of these alarm modes.
3–14 SP1 Range
SP1L (SP1 low limit value) and SP1H (SP1 high limit value) in the setup
menu are used to confine the adjustment range of SP1.
Example: A freezer is working in its normal temperature range -10°C to -15°C. In order
to avoid an abnormal set point, SP1L and SP1H are set with the following values:
SP1L=-15°C SP1H=-10°C
Now SP1 can only be adjusted within the range of -10°C to -15°C.
3–15 PV1 Shift
In certain applications it is desirable to shift the controller display value from its actual value. This can easily be accomplished by
using the PV1 shift function.
Press the “scroll” key to bring up the parameter SHIF. The value you adjust here, either positive or negative, will be added to the actu-
al value. The SHIF function will alter PV1 only.
Here is an example. A process is equipped with a heater, a sensor, and a subject to be warmed up. Due to the design and position of
the components in the system, the sensor could not be placed any closer to the part. Thermal gradient (different temperature) is com-
mon and necessary to an extent in any thermal system for heat to be transferred from one point to another. If the difference between
the sensor and the subject is 35°C, and the desired temperature at the subject to be heated is 200°C, the controlling value or the tem-
perature at the sensor should be 235°C. You should input -35°C so as to subtract 35°C from the actual process display. This in turn
will cause the controller to energize the load and bring the process display up to the set point value.
Sensor Break Alarm 1
Setup: A1FN=SENB
A1MD=NORM, LTCH
Hidden: TIME, A1SP, A1DV, A1HY
Sensor Break Alarm 2
Setup: OUT2=AL2
A2FN=SENB
A2MD=NORM, LTCH
Hidden: TIME, A2SP, A2DV, A2HY
Setup: SP1L, SP1H
Seitenansicht 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 91 92

Kommentare zu diesen Handbüchern

Keine Kommentare