
46
4–12 Pump Control
Pump control function is one of the
unique features of the TEC-9300.
Using this function, the pressure in
a process can be excellently con-
trolled. The pressure in a process is commonly generated by a
pump driven by a variable speed motor. The complete system has
the following characteristics which affect control behavior. 1. The
system is very noisy. 2. The pressure changes very rapidly. 3. The
pump characteristics are ultra nonlinear with respect to its speed.
4. The pump can’t generate any more pressure if its speed is lower
than half of its rating speed. 5. An ordinary pump may slowly lose
pressure even if the valves are completely closed.
Obviously, a conventional controller can’t fulfill the conditions
mentioned above. Only the superior noise rejection capability in
addition to the fast sampling rate possessed by the TEC-9300 can
handle such an application. To achieve this, set the following
parameters in the setup menu:
FUNC = FULL
EIFN = NONE
PVMD = PV1
FILT = 0.5
SELF = NONE
SPMD = PUMP
SP2F = DEVI
and program the following parameters in the user menu:
REFC = reference constant
SP2 = a negative value added to SP1 to obtain the set point for
the idle state
Since the pump can’t produce
any more pressure at lower
speeds, the pump may not
stop running even if the pres-
sure has reached the set point.
If this happens, the pump will
be overly worn and waste
additional power. To avoid
this, the TEC-9300 provides a
reference constant REFC in
the user menu. If PUMP is selected for SPMD, the controller will
periodically test the process by using this reference constant after
the pressure has reached its set point. If the test shows that the
pressure is still consumed by the process, the controller will con-
tinue to supply appropriate power to the pump. If the test shows
that the pressure is not consumed by the process, the controller
will gradually decrease the power to the pump until the pump
stops running. When this happens, the controller enters an idle
state. The idle state will use a lower set point which is obtained
by adding SP2 to SP1 until the pressure falls below this set point.
The idle state is provided for the purpose of preventing the pump
from been restarted too frequently. The value of SP2 should be
negative to ensure that the controller functions correctly.
The pump functions are summarized as follows:
1. If the process is demanding material (i.e., loses pressure), the
controller will precisely control the pressure at the set point.
2. If the process no longer consumes material, the controller will
shut off the pump for as long as possible.
3. The controller will restart the pump to control the pressure at
the set point as soon as the material is demanded again while
the pressure falls below a predetermined value (i.e., SP1+SP2).
Programming guide:
1. Perform auto-tuning to the system under such conditions that
the material (i.e., pressure) is exhausted at typical rate. A typi-
cal value for PB1 is about 10Kg/cm≈, TI1 is about 1 second,
TD1 is about 0.2 seconds.
2. If the process oscillates around the set point after auto-tuning,
then increase PB1 until the process can be stabilized at the set
point. The typical value of PB1 is about half to two times the
range of the pressure sensor.
3. Increasing FILT (filter) can further reduce the oscillation
amplitude. But a value of FILT higher than 5 (seconds) is not
recommended. A typical value for FILT is 0.5 or 1.
4. Close the valves and observe whether the controller can shut
off the pump each time. The value of REFC should be adjust-
ed as little as possible so that the controller can shut off the
pump each time when all the valves are closed. A typical value
for REFC is between 3 and 5.
5. An ordinary pump may slowly lose pressure even if the valves
are completely closed. Adjust SP2 according to the rule that a
more negative value of SP2 will allow the pump to be shut off
for a longer time when the valves are closed. A typical value
for SP2 is about -0.50Kg/cm≈.
An example for pump control is given in section 5-1.
4–13 Remote Lockout
The parameters can be locked to prevent them from being
changed by using either hard-
ware lockout (see section 1-3),
remote lockout, or both. If you
need the parameters to be
locked by using an external
switch (remote lockout func-
tion), then connect a switch to
terminals 13 and 14 (see sec-
tion 2-10), and choose LOCK for EIFN (see section 4-1).
If remote lockout is configured, all parameters will be locked
when the external switch is closed. When the switch is left open,
the lockout condition is determined by internal DIP switch (hard-
ware lockout, see section 1-3).
Hardware lockout: Can be used only during initial setup.
Remote lockout: Can be used any time.
Key menu
SPMD
SP2F
REFC
SP2
PUMP:
A cost effective solution
Pump control features:
1. Minimum oscillation of
pressure
2. Rapidly stabilized
3. Guaranteed pump stop
4. Programmable pump stop-
ping interval
Remote Lockout:
1. Connect external switch
to terminal and .
2. Set LOCK for EIFN
3. Lock all parameters
1413
Kommentare zu diesen Handbüchern