Connect-Tek Transa PRO 17 Bedienerhandbuch Seite 46

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 92
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 45
42
4–3 Second PID Set
In certain applications the character-
istics of a process are strongly relat-
ed to its process value. The TEC-
9300 provides two sets of PID val-
ues. When the process is changed to
a different set point, the PID values
can be switched to another set to
achieve optimum conditions.
Auto-tuning second PID
The optimal PID values for a
process may vary with its process
value and set point. Hence if a
process is used for a wide range of
set points, dual PID values are necessary to optimize control per-
formance. If the first PID set is selected (event input is not
applied) during auto-tuning procedure, the PID values will be
stored in PB1, TI1, and TD1. Similarly, if the second PID set is
selected (event input is applied while PID2 or SP.P2 is selected
for EIFN) during auto-tuning, the PID values will be stored in
PB2, TI2, and TD2 as soon as auto-tuning is completed.
Application 1: programmed by the set point
Choose SP.P2 for EIFN then both set point and PID values will
be switched to another set simultaneously.
The signal applied to the event input may
come from a timer, a PLC, an alarm relay, a
manual switch or other devices.
Application 2: programmed by
the process value
If the process value exceeds a certain limit,
500°C for example, it is desirable to use
another set of PID values to optimize con-
trol performance. You can use a process
high alarm to detect the limit of the process
value. Choose PV1H for A1FN, NORM for
A1MD, adjust A1SP to be equal to 500°C,
and choose PID2 for EIFN. If the tempera-
ture is higher than 500°C, then alarm 1 is activated. The alarm 1
output is connected to the event input, so the PID values will
change from PB1, TI1, and TD1 to PB2, TI2, and TD2.
Refer to section 5-9 for more details.
EIFN=SP.P2
EIFN=PID2
Alarm output
controls the
event input
Apply
Signal To
Event input +
Event input –
Setup
EIFN choose PID2 or
SP.P2
14
13
4–4 Ramp and Dwell
Ramp
The ramping function is performed
during power up as well as any
time the set point is changed.
Choose MINR or HRR for SPMD,
and the unit will perform the ramp-
ing function. The ramp rate is pro-
grammed by using RAMP, which
is found in the user menu.
Example without dwell timer
Select MINR for SPMD, °C for IN1U, 1-DP for DP1, and set
RAMP=10.0. SP1 is set to 200°C initially, then changed to 100°C
30 minutes after power up. The starting temperature is 30°C.
After power up, the process runs like the curve shown below:
Note: When the ramp function is used, the lower display will
show the current ramping value. However, it will revert to show
the set point value as soon as the up or down key is pressed for
adjustment. The ramping value is initiated as the process value
either at power up or when RAMP and/or the set point are
changed. Setting RAMP to zero means no ramp function at all.
Dwell
The dwell timer can be used
separately or in conjunction
with a ramp. If A1FN is set for
TIMR, alarm 1 will act as a
dwell timer. Similarly, alarm 2
will act as a dwell timer if A2FN is set for TIMR. The timer is
programmed by using TIME which is in the user menu. The timer
starts to count as soon as the process reaches its set point, and
triggers an alarm when it times out. Here is an example.
Example without ramp
Select TIMR for A1FN, °F for IN1U, NODP for DP1, and set
TIME=30.0. SP1 is set to 400°F initially, and corrected to 200°F
before the process reaches 200°F. When the process reaches the
set point (i.e., 200°F), the timer starts to count. The TIME value
can still be corrected without disturbing the timer before time out.
Example: TIME is changed to 40.0, 28 minutes after the process
has reached its set point. The behavior of the process value and
alarm 1 are shown below.
Once the timer output is energized, it will remain unchanged
until power down or an event input programmed for resetting
the alarm is applied.
Note: TIMR can’t be chosen for A1FN and A2FN simultaneous-
ly, or an error code will result.
4–4 Ramp and Dwell, continued next page…
Seitenansicht 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 91 92

Kommentare zu diesen Handbüchern

Keine Kommentare